Tripp Lite’s SmartOnline S3MX UPS series supports the continuous availability of your most important loads through all power conditions, providing a compact backup power platform that is easy to manage and inexpensive to operate. SmartOnline S3MX provides up to 200 kVA of clean, continuous power in a remarkably compact footprint. It is perfect for critical applications in IT, communications, corporate, commercial, retail, financial, security, transportation, emergency and light industrial environments.
Model | S3M30KX | S3M40KX | S3M60KX | S3M80KX | S3M100KX | S3M120KX | S3M160KX | S3M200KX |
---|---|---|---|---|---|---|---|---|
Capacity (VA) | 30 kVA | 40 kVA | 60 kVA | 80 kVA | 100 kVA | 120 kVA | 160 kVA | 200 kVA |
Capacity (Watts) | 27 kW | 36 kW | 54 kW | 72 kW | 90 kW | 108 kW | 144 kW | 180 kW |
INPUT | ||||||||
Nominal Voltage | Ph-Ph 380V/400V/415V (Ph-N 220V/230V/240V) | |||||||
Voltage Range | Ph-Ph 208-478V at < 50% Load; Ph-Ph 208-478V to 305-478V at 50% to 80% Load (Voltage Range Varies with Load); Ph-Ph 305-478V at > 80% Load | |||||||
Phase | 3-Phase with Neutral (3-Phase, Neutral + Ground) | |||||||
Power Factor (100% Load) | ≥ 0,99 | |||||||
OUTPUT | ||||||||
Nominal Voltage | Ph-Ph 380V/400V/415V (Ph-N 220V/230V/240V) | |||||||
AC Voltage Regulation (Double-Conversion Mode) | ±1% (Balanced Load) | |||||||
AC Voltage Regulation (Converter Mode or Battery Mode) | ±1% | |||||||
Power Factor | 0,9 | |||||||
AC Voltage Regulation (ECO Mode) | ± 11V of Nominal | ± 15V of Nominal | ||||||
Frequency | 46-54 Hz (50 Hz System); 56-64 Hz (60 Hz System) | Selectable ± 1 Hz, ± 2 Hz, ± 4 Hz of Input (Default: ± 4 Hz) | ||||||
Transfer Time (Line ‹—› Battery) | 0 ms | |||||||
Transfer Time (Inverter ‹—› Bypass) | Synchronous = 0 ms; Asynchronous < 4 ms | Synchronous = 0 ms; Asynchronous < 1 cycle | ||||||
Transfer Time (Inverter ‹—› ECO) | < 10 ms | < 20 ms | ||||||
BYPASS INPUT | ||||||||
Nominal Voltage | Ph-Ph 380V/400V/415V | |||||||
Phase | 3-Phase with Neutral (3-Phase, Neutral + Ground) | |||||||
Voltage Range | Upper Limit: Ph-N 231-264V Lower Limit: Ph-N 176-209V |
Upper Limit: +10%, +15% or +20% (Default: +15%) Lower Limit: -10%, -20% or -30% (Default: -20%) |
||||||
Nominal Frequency | 50/60 Hz (Auto-Selectable) | |||||||
Frequency Range | Selectable: ± 1-4 Hz (Default: ± 4 Hz) | Selectable: ± 1 Hz, ± 2 Hz, ± 4 Hz (Default: ± 4 Hz) | ||||||
Overload (Bypass Mode) | < 150% = 1 min | 105-110% = 1 h; 111-125% = 10 min; 126-150% = 1 min; > 150% = 200 ms |
||||||
EFFICIENCY | ||||||||
AC Line Mode | 94% at 100% Resistive Load; 93,5% at 50% Resistive Load | 94% at 100% Resistive Load; 93,5% at 50% Resistive Load | ||||||
ECO Mode | 98%, at 100% Resistive Load; 97,5% at 50% Resistive Load | 98% at 100% Resistive Load; 97% at 50% Resistive Load | ||||||
Battery Mode | 93,5% at 100% Resistive Load; 93% at 50% Resistive Load | 93% at 100% Resistive Load; 92,5% at 50% Resistive Load | ||||||
INTERNAL BATTERIES | ||||||||
Type | 12V Non-Spillable VRLA AGM/GEL | No Internal Batteries External Batteries Required for S3M30KX-NIB, S3M40KX-NIB, S3M60KX, S3M80KX, S3M100KX, S3M120KX, S3M160KX and S3M200KX |
||||||
Capacity | 9 Ah | 10 Ah | ||||||
Quantity | 80 (2 x Strings of 20 + 20) | |||||||
Runtime (50%/100% Load) | 17/5 min | 15/5 min | ||||||
EXTERNAL BATTERIES | ||||||||
Type | 12V Non-Spillable VRLA AGM/GEL | |||||||
DC Nominal Acceptance Voltage | ± 240 VDC | |||||||
Quantity | 40N (N ≥ 1 x Strings of 20 + 20) |